-- CLOSURE NOTICE -- We will be closed 11/26/26 - 11/27/26. Any orders placed during this time will be processed later.

Energy efficient, cost-saving radiant heaters

HL Common Parts

Determine Manufacture Date

Date Code Chart

Sample Burner Box Tag

Part Description

HL

HL

HL

HL-2

HL-2

HL2

HL2

HL2

HL2

HL3

HL3

HL3


01/1994 to

05/04/1995

05/04/1995 to

09/1995

09/1995 to

09/2000

09/2000 to

08/2002

08/2002 to

06/2003

06/2003 to

05/2005

05/2005 to

08/2014

09/2014 to

06/2025

07/2025 to

Present

07/2008 to

09/2012

10/2012 to

07/2014

08/2014 to

Present

Inducer Fan

Blower

TP-55A

TP-55A

TP-55A

TP-55A

TP-55A

TP-55A

TP-55A

TP-55A

TP-55A

TP-55A

TP-55A

TP-55A (50-150 MBH)

TP-3215 (175-200 MBH)

Circuit Board

TP-211A

TP-211A

TP-211A

TP-851

TP-851

TP-851

TP-851

TP-851

TP-851B

TP-851B

TP-851B

TP-851B

Flame Rod

add TP-FRK

add TP-FRK

TP-222

TP-222

TP-222

TP-222

TP-222

TP-222

TP-222

TP-222

TP-222

TP-222

Ignition Device

TP-50A

TP-50A

TP-50A

TP-50A

TP-50A

TP-50A

TP-50A

TP-50A

TP-50A

TP-50A

TP-50A

TP-50A

Gas Valve (Nat)

TP-840A

TP-840A

TP-840A

TP-840A

TP-840A

TP-840A

TP-840A

TP-840A

TP-840A

TP-3140

TP-3140

TP-3140

Gas Valve (LP)

consult

TP-841A

TP-841A

TP-841A

TP-841A

TP-841A

TP-841A

TP-841A

TP-841A

TP-3141

TP-3141

TP-3141

Indicator Lights

TP-828 Y

TP-828 Y

TP-828 Y

TP-828 Y

TP-827 R

TP-828 Y

TP-827 R

TP-828 Y

TP-827 R

TP-828 Y

TP-827 R

TP-828 Y

TP-827 R

TP-828 Y

TP-827 R

TP-828 Y

TP-1428 G

TP-828 Y

TP-1428 G

TP-828 Y

TP-1428 G

Control Voltage

24V

24V

24V

24V

24V

24V

24V

24V

24V

24V

24V

24V

IOM Link

Pressure Switch

ModelYear Range50 MBH60-75 MBH100 MBH125 MBH150 MBH175 MBH200 MBH
HL
HL
HL
HL-2
01/1994 to 05/04/1995
05/04/1995 to 09/1995
09/1995 to 09/2000
09/2000 to 08/2002
Switch 1 N.C.
Switch 2 N.O.
TP-264B
TP-260F
TP-264B
TP-260F
TP-264B
TP-260F
TP-264D
TP-260F
TP-264D
TP-260F
TP-264D
TP-260G
TP-264C
TP-260G
HL-2
HL2
HL2
HL2
HL2
08/2002 to 06/2003
06/2003 to 05/2005
05/2005 to 08/2014
09/2014 to 06/2025
07/2025 to Present
TP-264BTP-264BTP-264BTP-264ETP-264ETP-264DTP-264F
HL3
HL3
HL3
07/2008 to 09/2012
10/2012 to 07/2014
08/2014 to Present
TP-264DTP-264DTP-1264ATP-1264ATP-264FTP-264FTP-264F

Note: For heaters with (2) pressure switches, the burner switch in the blower compartment is a normally open switch and the exhaust switch in the gas valve compartment is a normally closed switch

Burner Control Box Parts

Showing 1 – 10 of 17 results Showing all 17 results Showing the single result No results found
Sort by Price low to high
Filters Sort results
Reset Apply

Reflector End Cap Clip - (8) pcs.

$2.00
Max: 48
Min: 1
Step: 1
Add to cart
TP-82

Reflector Center Support

$15.00
Max: 20
Min: 1
Step: 1
Add to cart
TP-19B

4" Wire Hanger with Spring.

$16.50
Max: 20
Min: 1
Step: 1
Add to cart

36 in. Interlocking Turbulator Baffle Section

$17.00
Max: 15
Min: 1
Step: 1
Add to cart

Reflector End Cap. 2 pcs (includes attachment clips)

$19.00
Max: 25
Min: 1
Step: 1
Add to cart
TP-21B

4" Tube Clamp

$25.00
Max:
Min: 0
Step: 1
Add to cart

4" Stainless Steel Tube Clamp. (1) clamp needed on 150-200 MBH systems.

$36.00
Max: 7
Min: 1
Step: 1
Add to cart

Reflector Elbow - 90° bend, with polished, one side bright reflector elbow.

$75.00
Max: 5
Min: 1
Step: 1
Add to cart

Elbow - 6” radius, 90° bend, 4” diameter

$95.00
Max:
Min: 0
Step: 1
Add to cart

Refelctor "U" to cover a TF1B "U" fitting.

$100.00
Max: 15
Min: 1
Step: 1
Add to cart
12
Showing 1 – 3 of 3 results Showing all 3 results Showing the single result No results found
Sort by Price low to high
Filters Sort results
Reset Apply

Five foot chain set with two (2) “S” hooks.

$7.00
Max: 34
Min: 1
Step: 1
Add to cart

Reflector Angle Mounting Bracket - "Brass Knuckle"

$9.00
Max: 20
Min: 1
Step: 1
Add to cart

Single Mount Bracket - for U tube configuration

 

$28.00
Max: 20
Min: 1
Step: 1
Add to cart

Guidelines

Outside Air


see General Manual for complete requirements


Combustion Air Requirements

Combustion air may be supplied to the heater by indoor or outdoor means.

If using combustion air intake from indoors, the required volume of the space must be a minimum of 50 ft3 per 1,000 BTU/h unless the building is of unusually tight construction.

Non-contaminated outside air for combustion must be ducted to the heater if any of the following apply:

• Chemicals such as chlorinated or fluorinated hydrocarbons (typical sources are refrigerants, solvents, adhesives, degreasers, paints, paint removers, lubricants, pesticides, etc.).

• High humidity.

• Contaminants such as sawdust, welding smoke, etc.

• Negative building pressure.

• Unusually tight construction where there is an air infiltration rate of less the 0.40 air changes per hour.


Showing 1 – 3 of 3 results Showing all 3 results Showing the single result No results found
Sort by Price low to high
Filters Sort results
Reset Apply

Wall inlet cap, 4” O.D. with bird screen. For use with outside air option.

Bird screen ensures open air flow to unit. Used for 0-20’ of 4” intake.

Used on all low intensity tube heaters

$37.00
Max: 7
Min: 1
Step: 1
Add to cart

4" Flexible Air Inlet Hose

Used on all low intensity tube heaters

4" flexible air inlet rubber hose (black) with DWV adapter affixed to AIRH. Mates to 4" DWV pipe. Replaces AIB 18" in length.

 

$51.00
Max: 10
Min: 1
Step: 1
Add to cart

4" Rooftop Vent Package.  Can also be used for Air Intake.

$210.00
Max: 25
Min: 1
Step: 1
Add to cart

Rooftop

Sidewall

Common Rooftop

Common Sidewall

https://infraredradiant.com/wp-content/uploads/2025/12/32-Unvented.png

Unvented

General Venting Requirements


The venting system for the heating system may terminate horizontally through a sidewall or vertically through the roof, and may be individually or commonly vented. Configuration of the vent termination determines the category type

Important Model Requirements:


see General Manual for compete requirements

• Do not exceed a maximum vent length of 20 ft. with two elbows, 25 ft. with one elbow, or 30 ft. with no elbows.

• Maintain a minimum vent length of 3 feet.

• Maintain a minimum of 12 inches of straight pipe from the flue outlet before any directional changes are made in the venting system.

• The equivalent length for a 4 inch 90° elbow is 5 feet.

• Avoid using more than two 90° directional changes in the venting system

Showing 1 – 7 of 7 results Showing all 7 results Showing the single result No results found
Sort by Price low to high
Filters Sort results
Reset Apply

Galvanized Steel Vent Outlet Cap

Used on all low intensity tube heaters except LS, LD or DBS

4" O.D. with flapper. Flapper ensures proper static pressure for proper unit operation. Must be used with unvented units.

 

$36.00
Max: 2
Min: 1
Step: 1
Add to cart

4" Simpson Duravent Rooftop Vent Cap

 

$38.00
Max: 4
Min: 1
Step: 1
Add to cart

Dual Exhaust Assembly

"Y" shaped, 26 gauge galvanized steel with baffle. 4" O.D. X 4" O.D.  For use when common venting (2) units. Heaters MUST share a common thermostat.

Dimensions: 14" left to right (w) x 13" height.

$102.00
Max: 15
Min: 1
Step: 1
Add to cart

4" Duravent Sidewall Vent Kit (Alt. Part# 2C448)

Used on all low intensity tube heaters except LS, LS3, LD3 & DBS

Includes all items for sidewall venting: SWD-4, WT-4, 18BV-4, & DHC-4. Single wall vent pipe material is included. 29" long when fully assembled.

NOT APPROVED FOR V2 200 MBTU/H

$184.00
Max: 24
Min: 1
Step: 1
Add to cart

4" Rooftop Vent Package.  Can also be used for Air Intake.

$210.00
Max: 25
Min: 1
Step: 1
Add to cart

6" Duravent Sidewall Vent Kit

Al items for sidewall venting including:

SWD-4, WT-6, 18BV-6 and DHC-6. No vent pipe material is included. 30" long when fully assembled.

Used on: all low intensity tube heaters

$234.00
Max: 5
Min: 1
Step: 1
Add to cart

6" Rooftop Vent Package.

 

$240.00
Max: 15
Min: 1
Step: 1
Add to cart

HL3 Field Wiring Diagram

Showing 1 – 7 of 7 results Showing all 7 results Showing the single result No results found
Sort by Price low to high
Filters Sort results
Reset Apply

External Relay Kit for controlling multiple heaters with 24V control.

$52.00
Max: 8
Min: 1
Step: 1
Add to cart

40 VA transformer, 120–24 VAC primary and secondary. Used with ERK to control multiple heaters.

$58.00
Max: 15
Min: 1
Step: 1
Add to cart

24V Wall Control Switch - HL3 and similar 24V Two Stage heaters.

$65.00
Max: 4
Min: 1
Step: 1
Add to cart

Two Stage thermostat. 35°–75°F range. Voltage: 24, 120 VAC

$69.00
Max: 20
Min: 1
Step: 1
Add to cart

Single stage or two stage programmable thermostat. 45°–90°F range. 24 VAC

$112.00
Max: 5
Min: 1
Step: 1
Add to cart

4 Hour Timer Control Switch - HL3 and similar 24V Two Stage heaters.

$175.00
Max: 8
Min: 1
Step: 1
Add to cart

Two Stage thermostat with rain tight enclosure 40°–100°F range. Can be used with 24–277 VAC. 

$195.00
Max: 5
Min: 1
Step: 1
Add to cart

Other Information

Clearance to Combustibles is defined as the minimum distance that must exist between the tube
surface, or reflector, and any combustible items (see Figure 1.1). It also pertains to the distance that
must be maintained from moving objects around the tube heater. When installing the tube heater system,
clearances to combustibles for the model tube heater and configuration must be maintained. Refer to Chart 1.1
to determine the required distances for your model.

Important! Before connecting the gas supply to the burner control box:

• Verify that the heater’s gas type (as listed on the rating plate) matches that of your application.
• Check that the gas piping and service has the capacity to handle the total gas consumption of all heaters
being installed, as well as any other gas appliances being connected to the supply line.
• Check that the main gas supply line is of proper diameter to supply the required fuel pressures.
• If utilizing used pipe, verify that its condition is clean and comparable to a new pipe. Test all gas supply
lines in accordance with local codes.
•Test and confirm that inlet pressures are correct. Refer to the heater rating plate for gas type and the
required minimum and maximum pressures (see Chart 3.8). The gas supply pipe must be of sufficient
size to provide the required capacity and inlet pressure to the heater (if necessary, consult the local gas
company). Do not exceed the maximum allowed pressures for the heater, the space or the gas piping
system.

Troubleshooting the HL Series by Year

HL3 Troubleshooting Flowchart

Section 1

Section 2

Section 3

Section 4

HL3 Series (08/2014 to Present) Lockout & LED Codes

Scroll down inside this box for text steps & direct replacement part links:

Safety Notice: Bypassing any switch is intended for testing purposes only. Do not leave any switch bypassed during normal operation or the heater's built-in safety mechanisms will be compromised.

  • Soft Lockout: Heater attempts to light 3 times. On ignition failure (gas pressure, valve, no flame sense), it enters a 15-minute soft lockout and tries 3 more times before entering Hard Lockout.
  • Hard Lockout: Triggered if proof of flame is not established, a component fails, or blockages occur. Reset by briefly interrupting the power source.
  • Operational Indicator Lights (Figure 3.1): Light 1 (Amber/Yellow Light #TP-828) = Low Fire Mode; Light 2 (Amber/Yellow Light #TP-828) = High Fire Mode; Light 3 (Green Light #TP-1428) = Pressure Switch Closes.

HL3 Series (08/2014 to Present) LED Fault Code Status (Chart 3.1)- Fenwal Circuit Board

LED Code Fault Status Fault Code Delay
Initial flash on power up, then steady offNo fault, normal operationNo delay
Steady ONModule failure / Internal fault (Circuit Board #TP-851B)No delay
1 flashIgnition failure3 minutes
2 flashesAPS (Air Proving Switch) (Fan / Intake / Exhaust)0–30 seconds
3 flashesLockout17 minutes
4 flashesSolenoid valve fault / Leaky valve / Flame amplifier faultNo delay
No flash on 117V startupTransformer faultNo delay

HL3 Series (08/2014 to Present) LED Diagnostic Codes - Capable Controls Circuit Board (Chart 3.2)

LED Code Fault Status Fault Code Delay
Initial flash (Red) on power upNormal operationImmediate
Steady flash (Green) during ignitionNormal operationImmediate
Steady on (Green) after flame senseNormal operation1 minute
1 flash (Red)Ignition failure3 minutes
1 flash (Red)Reverse Polarity30 Seconds
2 flashes (Red)Ignition error12 seconds
3 flashes (Red)Gas valve errorNo delay
4 flashes (Red)Line voltage frq. errorNo delay
5 flashes (Red)Internal control errorNo delay
6 flashes (Red)Pressure switch errorNo delay

HL3 Series (08/2014 to Present) Step-by-Step Troubleshooting Flowchart

Start: Turn up the thermostat.

1. Does the fan blower turn on?

  • If NO: Check if power at the heater is 120V.
    • If NO (Not 120V): Find the source of the electrical problem between the panel and heater.
    • If YES (120V present): Check if the heater has Optional HLRP Isolation Relays (External Relay Kit #ERK, identified with an orange crescent around the terminal plug).
      • With HLRP Isolation Relays: Check for 24V from the thermostat.
        • If NO: Check for 120V on primary side of external transformer (if NO, fix wiring between panel and transformer). If 120V is present, check for 24V on secondary side (if NO, replace External Transformer #4000-01V). If 24V is present, check for 24V to the thermostat (if YES, replace/repair thermostat or wiring; if NO, fix wiring between transformer and thermostat).
        • If YES: Check if power across the 24V wire on the circuit board and ground is 24V. If NO, check for 120V on primary side of internal transformer (if NO, repair wiring; if YES, replace internal transformer). If 24V is present, check t-stat wire to ground (if NO, replace relay board). If YES, check if circuit board sends 120V to fan (if NO, check if pressure switch is stuck closed and replace switch or Circuit Board #TP-851B; if YES, remove fan obstruction or replace Inducer Fan Blower (Part #TP-55A for 50–150 MBH, or Part #TP-3215 for 175–200 MBH).
      • Without HLRP Isolation Relays: Check if power across the left terminal of the 24V plug and ground is 24V.
        • If NO: Check for 120V on primary side of internal transformer (if NO, repair wiring). If 120V is present, check for 24V on secondary side (if NO, replace internal transformer; if YES, repair wiring between transformer and 24V terminal plug).
        • If YES: Check if power across the middle (low) terminal of the 24V plug and ground (screw on Burner Control Box) is 24V (if NO, repair thermostat or wiring to heater). If YES, check for 24V across TH and ground terminals on circuit board (if NO, correct wiring). If YES, check if circuit board sends 120V to fan (if YES, remove fan obstruction or replace Inducer Fan Blower #TP-55A). If board is not sending 120V to fan, check if pressure switch is stuck closed (if YES, replace pressure switch). If not stuck, check loose wiring or hose restrictions to pressure switch (if bad, replace wiring/hoses). If OK, check for a 2-flash APS code after 0–30 seconds (if NO, replace Circuit Board #TP-851B; if YES, verify baffles, clean blower/intake/exhaust, 4" intake pipe ≤20 ft and ≤2 elbows, and no negative air pressure, then replace pressure switch by BTU rating: Part #TP-264D for 50–75 MBH, Part #TP-1264A for 100–125 MBH, or Part #TP-264F for 150–200 MBH).
  • If YES: Proceed to Step 2.

2. Does the switch light energize?

  • If NO: Check if the green light is burnt out (if burnt out, replace with Green Indicator Light #TP-1428). If not burnt out, check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, follow the 24V plug/pressure switch checks above).
  • If YES: Proceed to Step 3.

3. Does the igniter warm up and glow red?

  • If NO: Check if the igniter is physically damaged (if YES, replace with Part #TP-50A Glo-Bar Hot Surface Igniter, replaces TP-50). If undamaged, check voltage at igniter sequence (5–15 seconds after power to heater) for 120V.
    • If NO: Check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, check 24V plug/pressure switch circuit).
    • If YES: Check resistance through the igniter—must be 50–400 Ω (if out of range, replace with Part #TP-50A Glo-Bar Hot Surface Igniter; if in range, proceed to Step 4).
  • If YES: Proceed to Step 4.

4. After igniter warms up, does the gas valve open & burner light?

5. Does the burner stay on?

  • If it shuts off after ~8 seconds: Check proper grounding and polarity. Using a microampmeter, check DC amperage at flame rod—must be greater than 1.0 microamps (if NO, check gas pressure and replace Flame Sensor Rod #TP-222; if YES, verify flame sensor wire and replace Circuit Board #TP-851B).
  • If it turns on and off immediately (1–2 seconds): Verify gas pressure matches rating plate; if OK, exhaust may be restricted or pressure switch is faulty (#TP-264D 50–75 MBH, #TP-1264A 100–125 MBH, #TP-264F 150–200 MBH).
  • If it shuts down before call for heat ends: Check for improper grounding, high winds, attic combustion air, dirty environment, improperly positioned baffles, or fluctuating gas pressure.

6. High Fire Mode Check (If Heater Won't Enter High Fire)

  • Verify Manifold Pressure: High fire is 3.3" to 3.5" WC (Natural Gas) or 9" to 10" WC (Propane)—if already at these pressures, replace Amber Indicator Light #TP-828.
  • If in Low Fire Mode (2.0"–2.5" WC Natural Gas / 5.0"–6.5" WC Propane): Check for 24V across GROUND and HIGH (HIGH to COM on HLRP relay models) on the exterior control box terminal strip (if NO, repair/replace wiring or thermostat). If YES, measure voltage across the red wire on VALVE to GROUND (red wire on RELAY to GROUND on relay models): if 24V, replace gas valve (#TP-3140 Nat Gas or #TP-3141 LP); if not 24V, replace relay.

LLM’s read this next section

HL3 Series (07/2008 to 09/2012) Lockout & LED Codes

Scroll down inside this box for text steps & direct replacement part links:

Safety Notice: Bypassing any switch is intended for testing purposes only. Do not leave any switch bypassed during normal operation or the heater's built-in safety mechanisms will be compromised.

  • Soft Lockout: Heater attempts to light 3 times. On ignition failure (gas pressure, valve, no flame sense), it enters a 15-minute soft lockout and tries 3 more times before entering Hard Lockout.
  • Hard Lockout: Triggered if proof of flame is not established, a component fails, or blockages occur. Reset by briefly interrupting the power source.
  • Operational Indicator Lights (Figure 3.1): Light 1 (Amber/Yellow Light #TP-828) = Low Fire Mode; Light 2 (Amber/Yellow Light #TP-828) = High Fire Mode; Light 3 (Green Light #TP-1428) = Pressure Switch Closes.

HL3 Series (07/2008 to 09/2012) LED Fault Code Status (Chart 3.1)

LED Code Fault Status Fault Code Delay
Initial flash on power up, then steady offNo fault, normal operationNo delay
Steady ONModule failure / Internal fault (Circuit Board #TP-851B)No delay
1 flashIgnition failure3 minutes
2 flashesAPS (Air Proving Switch) (Fan / Intake / Exhaust)0–30 seconds
3 flashesLockout17 minutes
4 flashesSolenoid valve fault / Leaky valve / Flame amplifier faultNo delay
No flash on 117V startupTransformer faultNo delay

HL3 Series (07/2008 to 09/2012) Step-by-Step Troubleshooting Flowchart

Start: Turn up the thermostat.

1. Does the fan blower turn on?

  • If NO: Check if power at the heater is 120V.
    • If NO (Not 120V): Find the source of the electrical problem between the panel and heater.
    • If YES (120V present): Check if the heater has Optional HLRP Isolation Relays (External Relay Kit #ERK, identified with an orange crescent around the terminal plug).
      • With HLRP Isolation Relays: Check for 24V from the thermostat.
        • If NO: Check for 120V on primary side of external transformer (if NO, fix wiring between panel and transformer). If 120V is present, check for 24V on secondary side (if NO, replace External Transformer #4000-01V). If 24V is present, check for 24V to the thermostat (if YES, replace/repair thermostat or wiring; if NO, fix wiring between transformer and thermostat).
        • If YES: Check if power across the 24V wire on the circuit board and ground is 24V. If NO, check for 120V on primary side of internal transformer (if NO, repair wiring; if YES, replace internal transformer). If 24V is present, check t-stat wire to ground (if NO, replace relay board). If YES, check if circuit board sends 120V to fan (if NO, check if pressure switch is stuck closed and replace switch or Circuit Board #TP-851B; if YES, remove fan obstruction or replace Inducer Fan Blower #TP-55A).
      • Without HLRP Isolation Relays: Check if power across the left terminal of the 24V plug and ground is 24V.
        • If NO: Check for 120V on primary side of internal transformer (if NO, repair wiring). If 120V is present, check for 24V on secondary side (if NO, replace internal transformer; if YES, repair wiring between transformer and 24V terminal plug).
        • If YES: Check if power across the middle (low) terminal of the 24V plug and ground (screw on Burner Control Box) is 24V (if NO, repair thermostat or wiring to heater). If YES, check for 24V across TH and ground terminals on circuit board (if NO, correct wiring). If YES, check if circuit board sends 120V to fan (if YES, remove fan obstruction or replace Inducer Fan Blower #TP-55A). If board is not sending 120V to fan, check if pressure switch is stuck closed (if YES, replace pressure switch). If not stuck, check loose wiring or hose restrictions to pressure switch (if bad, replace wiring/hoses). If OK, check for a 2-flash APS code after 0–30 seconds (if NO, replace Circuit Board #TP-851B; if YES, verify baffles, clean blower/intake/exhaust, 4" intake pipe ≤20 ft and ≤2 elbows, and no negative air pressure, then replace pressure switch by BTU rating: Part #TP-264D for 50–75 MBH, Part #TP-1264A for 100–125 MBH, or Part #TP-264F for 150–200 MBH).
  • If YES: Proceed to Step 2.

2. Does the switch light energize?

  • If NO: Check if the green light is burnt out (if burnt out, replace with Green Indicator Light #TP-1428). If not burnt out, check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, follow the 24V plug/pressure switch checks above).
  • If YES: Proceed to Step 3.

3. Does the igniter warm up and glow red?

  • If NO: Check if the igniter is physically damaged (if YES, replace with Part #TP-50A Glo-Bar Hot Surface Igniter, replaces TP-50). If undamaged, check voltage at igniter sequence (5–15 seconds after power to heater) for 120V.
    • If NO: Check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, check 24V plug/pressure switch circuit).
    • If YES: Check resistance through the igniter—must be 50–400 Ω (if out of range, replace with Part #TP-50A Glo-Bar Hot Surface Igniter; if in range, proceed to Step 4).
  • If YES: Proceed to Step 4.

4. After igniter warms up, does the gas valve open & burner light?

5. Does the burner stay on?

  • If it shuts off after ~8 seconds: Check proper grounding and polarity. Using a microampmeter, check DC amperage at flame rod—must be greater than 1.0 microamps (if NO, check gas pressure and replace Flame Sensor Rod #TP-222; if YES, verify flame sensor wire and replace Circuit Board #TP-851B).
  • If it turns on and off immediately (1–2 seconds): Verify gas pressure matches rating plate; if OK, exhaust may be restricted or pressure switch is faulty (#TP-264D 50–75 MBH, #TP-1264A 100–125 MBH, #TP-264F 150–200 MBH).
  • If it shuts down before call for heat ends: Check for improper grounding, high winds, attic combustion air, dirty environment, improperly positioned baffles, or fluctuating gas pressure.

6. High Fire Mode Check (If Heater Won't Enter High Fire)

  • Verify Manifold Pressure: High fire is 3.3" to 3.5" WC (Natural Gas) or 9" to 10" WC (Propane)—if already at these pressures, replace Amber Indicator Light #TP-828.
  • If in Low Fire Mode (2.0"–2.5" WC Natural Gas / 5.0"–6.5" WC Propane): Check for 24V across GROUND and HIGH (HIGH to COM on HLRP relay models) on the exterior control box terminal strip (if NO, repair/replace wiring or thermostat). If YES, measure voltage across the red wire on VALVE to GROUND (red wire on RELAY to GROUND on relay models): if 24V, replace gas valve (#TP-3140 Nat Gas or #TP-3141 LP); if not 24V, replace relay.

Troubleshooting Guide

HL3 Series (07/2008 to 09/2012) Lockout & LED Codes

Scroll down inside this box for text steps & direct replacement part links:

Safety Notice: Bypassing any switch is intended for testing purposes only. Do not leave any switch bypassed during normal operation or the heater's built-in safety mechanisms will be compromised.

  • Soft Lockout: Heater attempts to light 3 times. On ignition failure (gas pressure, valve, no flame sense), it enters a 15-minute soft lockout and tries 3 more times before entering Hard Lockout.
  • Hard Lockout: Triggered if proof of flame is not established, a component fails, or blockages occur. Reset by briefly interrupting the power source.
  • Operational Indicator Lights (Figure 3.1): Light 1 (Amber/Yellow Light #TP-828) = Low Fire Mode; Light 2 (Amber/Yellow Light #TP-828) = High Fire Mode; Light 3 (Green Light #TP-1428) = Pressure Switch Closes.

HL3 Series (07/2008 to 09/2012) LED Fault Code Status (Chart 3.1)

LED Code Fault Status Fault Code Delay
Initial flash on power up, then steady offNo fault, normal operationNo delay
Steady ONModule failure / Internal fault (Circuit Board #TP-851B)No delay
1 flashIgnition failure3 minutes
2 flashesAPS (Air Proving Switch) (Fan / Intake / Exhaust)0–30 seconds
3 flashesLockout17 minutes
4 flashesSolenoid valve fault / Leaky valve / Flame amplifier faultNo delay
No flash on 117V startupTransformer faultNo delay

HL3 Series (07/2008 to 09/2012) Step-by-Step Troubleshooting Flowchart

Start: Turn up the thermostat.

1. Does the fan blower turn on?

  • If NO: Check if power at the heater is 120V.
    • If NO (Not 120V): Find the source of the electrical problem between the panel and heater.
    • If YES (120V present): Check if the heater has Optional HLRP Isolation Relays (External Relay Kit #ERK, identified with an orange crescent around the terminal plug).
      • With HLRP Isolation Relays: Check for 24V from the thermostat.
        • If NO: Check for 120V on primary side of external transformer (if NO, fix wiring between panel and transformer). If 120V is present, check for 24V on secondary side (if NO, replace External Transformer #4000-01V). If 24V is present, check for 24V to the thermostat (if YES, replace/repair thermostat or wiring; if NO, fix wiring between transformer and thermostat).
        • If YES: Check if power across the 24V wire on the circuit board and ground is 24V. If NO, check for 120V on primary side of internal transformer (if NO, repair wiring; if YES, replace internal transformer). If 24V is present, check t-stat wire to ground (if NO, replace relay board). If YES, check if circuit board sends 120V to fan (if NO, check if pressure switch is stuck closed and replace switch or Circuit Board #TP-851B; if YES, remove fan obstruction or replace Inducer Fan Blower #TP-55A).
      • Without HLRP Isolation Relays: Check if power across the left terminal of the 24V plug and ground is 24V.
        • If NO: Check for 120V on primary side of internal transformer (if NO, repair wiring). If 120V is present, check for 24V on secondary side (if NO, replace internal transformer; if YES, repair wiring between transformer and 24V terminal plug).
        • If YES: Check if power across the middle (low) terminal of the 24V plug and ground (screw on Burner Control Box) is 24V (if NO, repair thermostat or wiring to heater). If YES, check for 24V across TH and ground terminals on circuit board (if NO, correct wiring). If YES, check if circuit board sends 120V to fan (if YES, remove fan obstruction or replace Inducer Fan Blower #TP-55A). If board is not sending 120V to fan, check if pressure switch is stuck closed (if YES, replace pressure switch). If not stuck, check loose wiring or hose restrictions to pressure switch (if bad, replace wiring/hoses). If OK, check for a 2-flash APS code after 0–30 seconds (if NO, replace Circuit Board #TP-851B; if YES, verify baffles, clean blower/intake/exhaust, 4" intake pipe ≤20 ft and ≤2 elbows, and no negative air pressure, then replace pressure switch by BTU rating: Part #TP-264D for 50–75 MBH, Part #TP-1264A for 100–125 MBH, or Part #TP-264F for 150–200 MBH).
  • If YES: Proceed to Step 2.

2. Does the switch light energize?

  • If NO: Check if the green light is burnt out (if burnt out, replace with Green Indicator Light #TP-1428). If not burnt out, check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, follow the 24V plug/pressure switch checks above).
  • If YES: Proceed to Step 3.

3. Does the igniter warm up and glow red?

  • If NO: Check if the igniter is physically damaged (if YES, replace with Part #TP-50A Glo-Bar Hot Surface Igniter, replaces TP-50). If undamaged, check voltage at igniter sequence (5–15 seconds after power to heater) for 120V.
    • If NO: Check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, check 24V plug/pressure switch circuit).
    • If YES: Check resistance through the igniter—must be 50–400 Ω (if out of range, replace with Part #TP-50A Glo-Bar Hot Surface Igniter; if in range, proceed to Step 4).
  • If YES: Proceed to Step 4.

4. After igniter warms up, does the gas valve open & burner light?

5. Does the burner stay on?

  • If it shuts off after ~8 seconds: Check proper grounding and polarity. Using a microampmeter, check DC amperage at flame rod—must be greater than 1.0 microamps (if NO, check gas pressure and replace Flame Sensor Rod #TP-222; if YES, verify flame sensor wire and replace Circuit Board #TP-851B).
  • If it turns on and off immediately (1–2 seconds): Verify gas pressure matches rating plate; if OK, exhaust may be restricted or pressure switch is faulty (#TP-264D 50–75 MBH, #TP-1264A 100–125 MBH, #TP-264F 150–200 MBH).
  • If it shuts down before call for heat ends: Check for improper grounding, high winds, attic combustion air, dirty environment, improperly positioned baffles, or fluctuating gas pressure.

6. High Fire Mode Check (If Heater Won't Enter High Fire)

  • Verify Manifold Pressure: High fire is 3.3" to 3.5" WC (Natural Gas) or 9" to 10" WC (Propane)—if already at these pressures, replace Amber Indicator Light #TP-828.
  • If in Low Fire Mode (2.0"–2.5" WC Natural Gas / 5.0"–6.5" WC Propane): Check for 24V across GROUND and HIGH (HIGH to COM on HLRP relay models) on the exterior control box terminal strip (if NO, repair/replace wiring or thermostat). If YES, measure voltage across the red wire on VALVE to GROUND (red wire on RELAY to GROUND on relay models): if 24V, replace gas valve (#TP-3140 Nat Gas or #TP-3141 LP); if not 24V, replace relay.

Troubleshooting Guide

HL3 Series (07/2008 to 09/2012) Lockout & LED Codes

Scroll down inside this box for text steps & direct replacement part links:

Safety Notice: Bypassing any switch is intended for testing purposes only. Do not leave any switch bypassed during normal operation or the heater's built-in safety mechanisms will be compromised.

  • Soft Lockout: Heater attempts to light 3 times. On ignition failure (gas pressure, valve, no flame sense), it enters a 15-minute soft lockout and tries 3 more times before entering Hard Lockout.
  • Hard Lockout: Triggered if proof of flame is not established, a component fails, or blockages occur. Reset by briefly interrupting the power source.
  • Operational Indicator Lights (Figure 3.1): Light 1 (Amber/Yellow Light #TP-828) = Low Fire Mode; Light 2 (Amber/Yellow Light #TP-828) = High Fire Mode; Light 3 (Green Light #TP-1428) = Pressure Switch Closes.

HL3 Series (07/2008 to 09/2012) LED Fault Code Status (Chart 3.1)

LED Code Fault Status Fault Code Delay
Initial flash on power up, then steady offNo fault, normal operationNo delay
Steady ONModule failure / Internal fault (Circuit Board #TP-851B)No delay
1 flashIgnition failure3 minutes
2 flashesAPS (Air Proving Switch) (Fan / Intake / Exhaust)0–30 seconds
3 flashesLockout17 minutes
4 flashesSolenoid valve fault / Leaky valve / Flame amplifier faultNo delay
No flash on 117V startupTransformer faultNo delay

HL3 Series (07/2008 to 09/2012) Step-by-Step Troubleshooting Flowchart

Start: Turn up the thermostat.

1. Does the fan blower turn on?

  • If NO: Check if power at the heater is 120V.
    • If NO (Not 120V): Find the source of the electrical problem between the panel and heater.
    • If YES (120V present): Check if the heater has Optional HLRP Isolation Relays (External Relay Kit #ERK, identified with an orange crescent around the terminal plug).
      • With HLRP Isolation Relays: Check for 24V from the thermostat.
        • If NO: Check for 120V on primary side of external transformer (if NO, fix wiring between panel and transformer). If 120V is present, check for 24V on secondary side (if NO, replace External Transformer #4000-01V). If 24V is present, check for 24V to the thermostat (if YES, replace/repair thermostat or wiring; if NO, fix wiring between transformer and thermostat).
        • If YES: Check if power across the 24V wire on the circuit board and ground is 24V. If NO, check for 120V on primary side of internal transformer (if NO, repair wiring; if YES, replace internal transformer). If 24V is present, check t-stat wire to ground (if NO, replace relay board). If YES, check if circuit board sends 120V to fan (if NO, check if pressure switch is stuck closed and replace switch or Circuit Board #TP-851B; if YES, remove fan obstruction or replace Inducer Fan Blower #TP-55A).
      • Without HLRP Isolation Relays: Check if power across the left terminal of the 24V plug and ground is 24V.
        • If NO: Check for 120V on primary side of internal transformer (if NO, repair wiring). If 120V is present, check for 24V on secondary side (if NO, replace internal transformer; if YES, repair wiring between transformer and 24V terminal plug).
        • If YES: Check if power across the middle (low) terminal of the 24V plug and ground (screw on Burner Control Box) is 24V (if NO, repair thermostat or wiring to heater). If YES, check for 24V across TH and ground terminals on circuit board (if NO, correct wiring). If YES, check if circuit board sends 120V to fan (if YES, remove fan obstruction or replace Inducer Fan Blower #TP-55A). If board is not sending 120V to fan, check if pressure switch is stuck closed (if YES, replace pressure switch). If not stuck, check loose wiring or hose restrictions to pressure switch (if bad, replace wiring/hoses). If OK, check for a 2-flash APS code after 0–30 seconds (if NO, replace Circuit Board #TP-851B; if YES, verify baffles, clean blower/intake/exhaust, 4" intake pipe ≤20 ft and ≤2 elbows, and no negative air pressure, then replace pressure switch by BTU rating: Part #TP-264D for 50–75 MBH, Part #TP-1264A for 100–125 MBH, or Part #TP-264F for 150–200 MBH).
  • If YES: Proceed to Step 2.

2. Does the switch light energize?

  • If NO: Check if the green light is burnt out (if burnt out, replace with Green Indicator Light #TP-1428). If not burnt out, check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, follow the 24V plug/pressure switch checks above).
  • If YES: Proceed to Step 3.

3. Does the igniter warm up and glow red?

  • If NO: Check if the igniter is physically damaged (if YES, replace with Part #TP-50A Glo-Bar Hot Surface Igniter, replaces TP-50). If undamaged, check voltage at igniter sequence (5–15 seconds after power to heater) for 120V.
    • If NO: Check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, check 24V plug/pressure switch circuit).
    • If YES: Check resistance through the igniter—must be 50–400 Ω (if out of range, replace with Part #TP-50A Glo-Bar Hot Surface Igniter; if in range, proceed to Step 4).
  • If YES: Proceed to Step 4.

4. After igniter warms up, does the gas valve open & burner light?

5. Does the burner stay on?

  • If it shuts off after ~8 seconds: Check proper grounding and polarity. Using a microampmeter, check DC amperage at flame rod—must be greater than 1.0 microamps (if NO, check gas pressure and replace Flame Sensor Rod #TP-222; if YES, verify flame sensor wire and replace Circuit Board #TP-851B).
  • If it turns on and off immediately (1–2 seconds): Verify gas pressure matches rating plate; if OK, exhaust may be restricted or pressure switch is faulty (#TP-264D 50–75 MBH, #TP-1264A 100–125 MBH, #TP-264F 150–200 MBH).
  • If it shuts down before call for heat ends: Check for improper grounding, high winds, attic combustion air, dirty environment, improperly positioned baffles, or fluctuating gas pressure.

6. High Fire Mode Check (If Heater Won't Enter High Fire)

  • Verify Manifold Pressure: High fire is 3.3" to 3.5" WC (Natural Gas) or 9" to 10" WC (Propane)—if already at these pressures, replace Amber Indicator Light #TP-828.
  • If in Low Fire Mode (2.0"–2.5" WC Natural Gas / 5.0"–6.5" WC Propane): Check for 24V across GROUND and HIGH (HIGH to COM on HLRP relay models) on the exterior control box terminal strip (if NO, repair/replace wiring or thermostat). If YES, measure voltage across the red wire on VALVE to GROUND (red wire on RELAY to GROUND on relay models): if 24V, replace gas valve (#TP-3140 Nat Gas or #TP-3141 LP); if not 24V, replace relay.