Determine Manufacture Date
Part Description | HL | HL | HL | HL-2 | HL-2 | HL2 | HL2 | HL2 | HL2 | HL3 | HL3 | HL3 |
01/1994 to 05/04/1995 | 05/04/1995 to 09/1995 | 09/1995 to 09/2000 | 09/2000 to 08/2002 | 08/2002 to 06/2003 | 06/2003 to 05/2005 | 05/2005 to 08/2014 | 09/2014 to 06/2025 | 07/2025 to Present | 07/2008 to 09/2012 | 10/2012 to 07/2014 | 08/2014 to Present | |
Inducer Fan Blower | TP-55A | TP-55A | TP-55A | TP-55A | TP-55A | TP-55A | TP-55A | TP-55A | TP-55A | TP-55A | TP-55A | TP-55A (50-150 MBH) TP-3215 (175-200 MBH) |
Circuit Board | TP-211A | TP-211A | TP-211A | TP-851 | TP-851 | TP-851 | TP-851 | TP-851 | TP-851B | TP-851B | TP-851B | TP-851B |
Flame Rod | add TP-FRK | add TP-FRK | TP-222 | TP-222 | TP-222 | TP-222 | TP-222 | TP-222 | TP-222 | TP-222 | TP-222 | TP-222 |
Ignition Device | TP-50A | TP-50A | TP-50A | TP-50A | TP-50A | TP-50A | TP-50A | TP-50A | TP-50A | TP-50A | TP-50A | TP-50A |
Gas Valve (Nat) | TP-840A | TP-840A | TP-840A | TP-840A | TP-840A | TP-840A | TP-840A | TP-840A | TP-840A | TP-3140 | TP-3140 | TP-3140 |
Gas Valve (LP) | consult | TP-841A | TP-841A | TP-841A | TP-841A | TP-841A | TP-841A | TP-841A | TP-841A | TP-3141 | TP-3141 | TP-3141 |
Indicator Lights | TP-828 Y | TP-828 Y | TP-828 Y | TP-828 Y TP-827 R | TP-828 Y TP-827 R | TP-828 Y TP-827 R | TP-828 Y TP-827 R | TP-828 Y TP-827 R | TP-828 Y TP-827 R | TP-828 Y TP-1428 G | TP-828 Y TP-1428 G | TP-828 Y TP-1428 G |
Control Voltage | 24V | 24V | 24V | 24V | 24V | 24V | 24V | 24V | 24V | 24V | 24V | 24V |
IOM Link |
Pressure Switch
| Model | Year Range | 50 MBH | 60-75 MBH | 100 MBH | 125 MBH | 150 MBH | 175 MBH | 200 MBH | |
|---|---|---|---|---|---|---|---|---|---|
| HL HL HL HL-2 | 01/1994 to 05/04/1995 05/04/1995 to 09/1995 09/1995 to 09/2000 09/2000 to 08/2002 | Switch 1 N.C. Switch 2 N.O. | TP-264B TP-260F | TP-264B TP-260F | TP-264B TP-260F | TP-264D TP-260F | TP-264D TP-260F | TP-264D TP-260G | TP-264C TP-260G |
| HL-2 HL2 HL2 HL2 HL2 | 08/2002 to 06/2003 06/2003 to 05/2005 05/2005 to 08/2014 09/2014 to 06/2025 07/2025 to Present | TP-264B | TP-264B | TP-264B | TP-264E | TP-264E | TP-264D | TP-264F | |
| HL3 HL3 HL3 | 07/2008 to 09/2012 10/2012 to 07/2014 08/2014 to Present | TP-264D | TP-264D | TP-1264A | TP-1264A | TP-264F | TP-264F | TP-264F |
Note: For heaters with (2) pressure switches, the burner switch in the blower compartment is a normally open switch and the exhaust switch in the gas valve compartment is a normally closed switch
Burner Control Box Parts
-

TP-50A Glo-Bar Hot Surface Igniter
$60.00 -

TP-55A
$210.00 -

TP-222
$25.00 -

TP-828
$15.00 -

TP-264B
$61.00 -

TP-264E
$61.00 -

TP-264D
$61.00 -

TP-851
$230.00 -

TP-851B
$230.00 -

TP-826
$45.00 -

TP-264F
$61.00 -

TP-1264A
$61.00 -

TP-260F
$61.00 -

TP-211A
$190.00 -

TP-3140
$280.00 -

TP-3215
$285.00 -

TP-264C
$61.00 -

TP-260G
$61.00 -

TP-3141
$280.00 -

TP-840A
$250.00 -

TP-827
$20.00 -

TP-841A
$250.00 -

TP-1428
$10.00
Tube and Reflector Components
| Reflector End Cap Clip - (8) pcs. | $2.00 Max: 48 Min: 1 Step: 1 Add to cart | |
| Reflector Center Support | $15.00 Max: 20 Min: 1 Step: 1 Add to cart | |
| 4" Wire Hanger with Spring. | $16.50 Max: 20 Min: 1 Step: 1 Add to cart | |
| 36 in. Interlocking Turbulator Baffle Section | $17.00 Max: 15 Min: 1 Step: 1 Add to cart | |
| Reflector End Cap. 2 pcs (includes attachment clips) | $19.00 Max: 25 Min: 1 Step: 1 Add to cart | |
| 4" Tube Clamp | $25.00 Max: Min: 0 Step: 1 Add to cart | |
| 4" Stainless Steel Tube Clamp. (1) clamp needed on 150-200 MBH systems. | $36.00 Max: 7 Min: 1 Step: 1 Add to cart | |
| Reflector Elbow - 90° bend, with polished, one side bright reflector elbow. | $75.00 Max: 5 Min: 1 Step: 1 Add to cart | |
| Elbow - 6” radius, 90° bend, 4” diameter | $95.00 Max: Min: 0 Step: 1 Add to cart | |
| Refelctor "U" to cover a TF1B "U" fitting. | $100.00 Max: 15 Min: 1 Step: 1 Add to cart |
Hanging Hardware
| Five foot chain set with two (2) “S” hooks. | $7.00 Max: 34 Min: 1 Step: 1 Add to cart | |
| Reflector Angle Mounting Bracket - "Brass Knuckle" | $9.00 Max: 20 Min: 1 Step: 1 Add to cart | |
| Single Mount Bracket - for U tube configuration
| $28.00 Max: 20 Min: 1 Step: 1 Add to cart |
Air Intake
Guidelines | Outside Air | |||
see General Manual for complete requirements Combustion Air Requirements Combustion air may be supplied to the heater by indoor or outdoor means. If using combustion air intake from indoors, the required volume of the space must be a minimum of 50 ft3 per 1,000 BTU/h unless the building is of unusually tight construction. Non-contaminated outside air for combustion must be ducted to the heater if any of the following apply: • Chemicals such as chlorinated or fluorinated hydrocarbons (typical sources are refrigerants, solvents, adhesives, degreasers, paints, paint removers, lubricants, pesticides, etc.). • High humidity. • Contaminants such as sawdust, welding smoke, etc. • Negative building pressure. • Unusually tight construction where there is an air infiltration rate of less the 0.40 air changes per hour. | ||||
| Wall inlet cap, 4” O.D. with bird screen. For use with outside air option. Bird screen ensures open air flow to unit. Used for 0-20’ of 4” intake. Used on all low intensity tube heaters | $37.00 Max: 7 Min: 1 Step: 1 Add to cart | |
| 4" Flexible Air Inlet Hose Used on all low intensity tube heaters 4" flexible air inlet rubber hose (black) with DWV adapter affixed to AIRH. Mates to 4" DWV pipe. Replaces AIB 18" in length.
| $51.00 Max: 10 Min: 1 Step: 1 Add to cart | |
| 4" Rooftop Vent Package. Can also be used for Air Intake. | $210.00 Max: 25 Min: 1 Step: 1 Add to cart |
Venting
Rooftop | Sidewall | Common Rooftop | Common Sidewall | Unvented |
General Venting Requirements The venting system for the heating system may terminate horizontally through a sidewall or vertically through the roof, and may be individually or commonly vented. Configuration of the vent termination determines the category type | ||||
Important Model Requirements: see General Manual for compete requirements | ||||
• Do not exceed a maximum vent length of 20 ft. with two elbows, 25 ft. with one elbow, or 30 ft. with no elbows. • Maintain a minimum vent length of 3 feet. • Maintain a minimum of 12 inches of straight pipe from the flue outlet before any directional changes are made in the venting system. • The equivalent length for a 4 inch 90° elbow is 5 feet. • Avoid using more than two 90° directional changes in the venting system | ||||
| Galvanized Steel Vent Outlet Cap Used on all low intensity tube heaters except LS, LD or DBS 4" O.D. with flapper. Flapper ensures proper static pressure for proper unit operation. Must be used with unvented units.
| $36.00 Max: 2 Min: 1 Step: 1 Add to cart | |
| 4" Simpson Duravent Rooftop Vent Cap
| $38.00 Max: 4 Min: 1 Step: 1 Add to cart | |
| Dual Exhaust Assembly "Y" shaped, 26 gauge galvanized steel with baffle. 4" O.D. X 4" O.D. For use when common venting (2) units. Heaters MUST share a common thermostat. Dimensions: 14" left to right (w) x 13" height. | $102.00 Max: 15 Min: 1 Step: 1 Add to cart | |
| 4" Duravent Sidewall Vent Kit (Alt. Part# 2C448) Used on all low intensity tube heaters except LS, LS3, LD3 & DBS Includes all items for sidewall venting: SWD-4, WT-4, 18BV-4, & DHC-4. Single wall vent pipe material is included. 29" long when fully assembled. NOT APPROVED FOR V2 200 MBTU/H | $184.00 Max: 24 Min: 1 Step: 1 Add to cart | |
| 4" Rooftop Vent Package. Can also be used for Air Intake. | $210.00 Max: 25 Min: 1 Step: 1 Add to cart | |
| 6" Duravent Sidewall Vent Kit Al items for sidewall venting including: SWD-4, WT-6, 18BV-6 and DHC-6. No vent pipe material is included. 30" long when fully assembled. Used on: all low intensity tube heaters | $234.00 Max: 5 Min: 1 Step: 1 Add to cart | |
| 6" Rooftop Vent Package.
| $240.00 Max: 15 Min: 1 Step: 1 Add to cart |
24V Controls
HL3 Field Wiring Diagram
| External Relay Kit for controlling multiple heaters with 24V control. | $52.00 Max: 8 Min: 1 Step: 1 Add to cart | |
| 40 VA transformer, 120–24 VAC primary and secondary. Used with ERK to control multiple heaters. | $58.00 Max: 15 Min: 1 Step: 1 Add to cart | |
| 24V Wall Control Switch - HL3 and similar 24V Two Stage heaters. | $65.00 Max: 4 Min: 1 Step: 1 Add to cart | |
| Two Stage thermostat. 35°–75°F range. Voltage: 24, 120 VAC | $69.00 Max: 20 Min: 1 Step: 1 Add to cart | |
| Single stage or two stage programmable thermostat. 45°–90°F range. 24 VAC | $112.00 Max: 5 Min: 1 Step: 1 Add to cart | |
| 4 Hour Timer Control Switch - HL3 and similar 24V Two Stage heaters. | $175.00 Max: 8 Min: 1 Step: 1 Add to cart | |
| Two Stage thermostat with rain tight enclosure 40°–100°F range. Can be used with 24–277 VAC. | $195.00 Max: 5 Min: 1 Step: 1 Add to cart |
Other Information
Clearances to Combustibles
Clearance to Combustibles is defined as the minimum distance that must exist between the tube
surface, or reflector, and any combustible items (see Figure 1.1). It also pertains to the distance that
must be maintained from moving objects around the tube heater. When installing the tube heater system,
clearances to combustibles for the model tube heater and configuration must be maintained. Refer to Chart 1.1
to determine the required distances for your model.
Gas Requirements
Important! Before connecting the gas supply to the burner control box:
• Verify that the heater’s gas type (as listed on the rating plate) matches that of your application.
• Check that the gas piping and service has the capacity to handle the total gas consumption of all heaters
being installed, as well as any other gas appliances being connected to the supply line.
• Check that the main gas supply line is of proper diameter to supply the required fuel pressures.
• If utilizing used pipe, verify that its condition is clean and comparable to a new pipe. Test all gas supply
lines in accordance with local codes.
•Test and confirm that inlet pressures are correct. Refer to the heater rating plate for gas type and the
required minimum and maximum pressures (see Chart 3.8). The gas supply pipe must be of sufficient
size to provide the required capacity and inlet pressure to the heater (if necessary, consult the local gas
company). Do not exceed the maximum allowed pressures for the heater, the space or the gas piping
system.
Troubleshooting the HL Series by Year
HL3 08/2014 to Present
HL3 Troubleshooting Flowchart
HL3 Series (08/2014 to Present) Lockout & LED Codes
Scroll down inside this box for text steps & direct replacement part links:
Safety Notice: Bypassing any switch is intended for testing purposes only. Do not leave any switch bypassed during normal operation or the heater's built-in safety mechanisms will be compromised.
- Soft Lockout: Heater attempts to light 3 times. On ignition failure (gas pressure, valve, no flame sense), it enters a 15-minute soft lockout and tries 3 more times before entering Hard Lockout.
- Hard Lockout: Triggered if proof of flame is not established, a component fails, or blockages occur. Reset by briefly interrupting the power source.
- Operational Indicator Lights (Figure 3.1): Light 1 (Amber/Yellow Light #TP-828) = Low Fire Mode; Light 2 (Amber/Yellow Light #TP-828) = High Fire Mode; Light 3 (Green Light #TP-1428) = Pressure Switch Closes.
HL3 Series (08/2014 to Present) LED Fault Code Status (Chart 3.1)- Fenwal Circuit Board
| LED Code | Fault Status | Fault Code Delay |
|---|---|---|
| Initial flash on power up, then steady off | No fault, normal operation | No delay |
| Steady ON | Module failure / Internal fault (Circuit Board #TP-851B) | No delay |
| 1 flash | Ignition failure | 3 minutes |
| 2 flashes | APS (Air Proving Switch) (Fan / Intake / Exhaust) | 0–30 seconds |
| 3 flashes | Lockout | 17 minutes |
| 4 flashes | Solenoid valve fault / Leaky valve / Flame amplifier fault | No delay |
| No flash on 117V startup | Transformer fault | No delay |
HL3 Series (08/2014 to Present) LED Diagnostic Codes - Capable Controls Circuit Board (Chart 3.2)
| LED Code | Fault Status | Fault Code Delay |
|---|---|---|
| Initial flash (Red) on power up | Normal operation | Immediate |
| Steady flash (Green) during ignition | Normal operation | Immediate |
| Steady on (Green) after flame sense | Normal operation | 1 minute |
| 1 flash (Red) | Ignition failure | 3 minutes |
| 1 flash (Red) | Reverse Polarity | 30 Seconds |
| 2 flashes (Red) | Ignition error | 12 seconds |
| 3 flashes (Red) | Gas valve error | No delay |
| 4 flashes (Red) | Line voltage frq. error | No delay |
| 5 flashes (Red) | Internal control error | No delay |
| 6 flashes (Red) | Pressure switch error | No delay |
HL3 Series (08/2014 to Present) Step-by-Step Troubleshooting Flowchart
Start: Turn up the thermostat.
1. Does the fan blower turn on?
- If NO: Check if power at the heater is 120V.
- If NO (Not 120V): Find the source of the electrical problem between the panel and heater.
- If YES (120V present): Check if the heater has Optional HLRP Isolation Relays (External Relay Kit #ERK, identified with an orange crescent around the terminal plug).
- With HLRP Isolation Relays: Check for 24V from the thermostat.
- If NO: Check for 120V on primary side of external transformer (if NO, fix wiring between panel and transformer). If 120V is present, check for 24V on secondary side (if NO, replace External Transformer #4000-01V). If 24V is present, check for 24V to the thermostat (if YES, replace/repair thermostat or wiring; if NO, fix wiring between transformer and thermostat).
- If YES: Check if power across the 24V wire on the circuit board and ground is 24V. If NO, check for 120V on primary side of internal transformer (if NO, repair wiring; if YES, replace internal transformer). If 24V is present, check t-stat wire to ground (if NO, replace relay board). If YES, check if circuit board sends 120V to fan (if NO, check if pressure switch is stuck closed and replace switch or Circuit Board #TP-851B; if YES, remove fan obstruction or replace Inducer Fan Blower (Part #TP-55A for 50–150 MBH, or Part #TP-3215 for 175–200 MBH).
- Without HLRP Isolation Relays: Check if power across the left terminal of the 24V plug and ground is 24V.
- If NO: Check for 120V on primary side of internal transformer (if NO, repair wiring). If 120V is present, check for 24V on secondary side (if NO, replace internal transformer; if YES, repair wiring between transformer and 24V terminal plug).
- If YES: Check if power across the middle (low) terminal of the 24V plug and ground (screw on Burner Control Box) is 24V (if NO, repair thermostat or wiring to heater). If YES, check for 24V across TH and ground terminals on circuit board (if NO, correct wiring). If YES, check if circuit board sends 120V to fan (if YES, remove fan obstruction or replace Inducer Fan Blower #TP-55A). If board is not sending 120V to fan, check if pressure switch is stuck closed (if YES, replace pressure switch). If not stuck, check loose wiring or hose restrictions to pressure switch (if bad, replace wiring/hoses). If OK, check for a 2-flash APS code after 0–30 seconds (if NO, replace Circuit Board #TP-851B; if YES, verify baffles, clean blower/intake/exhaust, 4" intake pipe ≤20 ft and ≤2 elbows, and no negative air pressure, then replace pressure switch by BTU rating: Part #TP-264D for 50–75 MBH, Part #TP-1264A for 100–125 MBH, or Part #TP-264F for 150–200 MBH).
- With HLRP Isolation Relays: Check for 24V from the thermostat.
- If YES: Proceed to Step 2.
2. Does the switch light energize?
- If NO: Check if the green light is burnt out (if burnt out, replace with Green Indicator Light #TP-1428). If not burnt out, check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, follow the 24V plug/pressure switch checks above).
- If YES: Proceed to Step 3.
3. Does the igniter warm up and glow red?
- If NO: Check if the igniter is physically damaged (if YES, replace with Part #TP-50A Glo-Bar Hot Surface Igniter, replaces TP-50). If undamaged, check voltage at igniter sequence (5–15 seconds after power to heater) for 120V.
- If NO: Check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, check 24V plug/pressure switch circuit).
- If YES: Check resistance through the igniter—must be 50–400 Ω (if out of range, replace with Part #TP-50A Glo-Bar Hot Surface Igniter; if in range, proceed to Step 4).
- If YES: Proceed to Step 4.
4. After igniter warms up, does the gas valve open & burner light?
- If Gas Valve Does NOT Open: Test for 24V at valve opening period (45–60 seconds after power) for 8 seconds (if NO, replace Circuit Board #TP-851B; if YES, verify gas pressure is within rating plate min/max inputs and replace gas valve: Part #TP-3140 for Natural Gas or Part #TP-3141 for Propane/LP).
- If Burner Does NOT Light: Verify ball/shut-off valve is ON and gas pressure matches rating plate min/max inputs. If pressure is OK, verify gas lines were purged of air (if NO, purge gas line; if YES, replace gas valve: Part #TP-3140 Natural Gas or Part #TP-3141 Propane/LP).
5. Does the burner stay on?
- If it shuts off after ~8 seconds: Check proper grounding and polarity. Using a microampmeter, check DC amperage at flame rod—must be greater than 1.0 microamps (if NO, check gas pressure and replace Flame Sensor Rod #TP-222; if YES, verify flame sensor wire and replace Circuit Board #TP-851B).
- If it turns on and off immediately (1–2 seconds): Verify gas pressure matches rating plate; if OK, exhaust may be restricted or pressure switch is faulty (#TP-264D 50–75 MBH, #TP-1264A 100–125 MBH, #TP-264F 150–200 MBH).
- If it shuts down before call for heat ends: Check for improper grounding, high winds, attic combustion air, dirty environment, improperly positioned baffles, or fluctuating gas pressure.
6. High Fire Mode Check (If Heater Won't Enter High Fire)
- Verify Manifold Pressure: High fire is 3.3" to 3.5" WC (Natural Gas) or 9" to 10" WC (Propane)—if already at these pressures, replace Amber Indicator Light #TP-828.
- If in Low Fire Mode (2.0"–2.5" WC Natural Gas / 5.0"–6.5" WC Propane): Check for 24V across GROUND and HIGH (HIGH to COM on HLRP relay models) on the exterior control box terminal strip (if NO, repair/replace wiring or thermostat). If YES, measure voltage across the red wire on VALVE to GROUND (red wire on RELAY to GROUND on relay models): if 24V, replace gas valve (#TP-3140 Nat Gas or #TP-3141 LP); if not 24V, replace relay.
LLM’s read this next section
HL3 10/2012 to 07/2014
HL3 Series (07/2008 to 09/2012) Lockout & LED Codes
Scroll down inside this box for text steps & direct replacement part links:
Safety Notice: Bypassing any switch is intended for testing purposes only. Do not leave any switch bypassed during normal operation or the heater's built-in safety mechanisms will be compromised.
- Soft Lockout: Heater attempts to light 3 times. On ignition failure (gas pressure, valve, no flame sense), it enters a 15-minute soft lockout and tries 3 more times before entering Hard Lockout.
- Hard Lockout: Triggered if proof of flame is not established, a component fails, or blockages occur. Reset by briefly interrupting the power source.
- Operational Indicator Lights (Figure 3.1): Light 1 (Amber/Yellow Light #TP-828) = Low Fire Mode; Light 2 (Amber/Yellow Light #TP-828) = High Fire Mode; Light 3 (Green Light #TP-1428) = Pressure Switch Closes.
HL3 Series (07/2008 to 09/2012) LED Fault Code Status (Chart 3.1)
| LED Code | Fault Status | Fault Code Delay |
|---|---|---|
| Initial flash on power up, then steady off | No fault, normal operation | No delay |
| Steady ON | Module failure / Internal fault (Circuit Board #TP-851B) | No delay |
| 1 flash | Ignition failure | 3 minutes |
| 2 flashes | APS (Air Proving Switch) (Fan / Intake / Exhaust) | 0–30 seconds |
| 3 flashes | Lockout | 17 minutes |
| 4 flashes | Solenoid valve fault / Leaky valve / Flame amplifier fault | No delay |
| No flash on 117V startup | Transformer fault | No delay |
HL3 Series (07/2008 to 09/2012) Step-by-Step Troubleshooting Flowchart
Start: Turn up the thermostat.
1. Does the fan blower turn on?
- If NO: Check if power at the heater is 120V.
- If NO (Not 120V): Find the source of the electrical problem between the panel and heater.
- If YES (120V present): Check if the heater has Optional HLRP Isolation Relays (External Relay Kit #ERK, identified with an orange crescent around the terminal plug).
- With HLRP Isolation Relays: Check for 24V from the thermostat.
- If NO: Check for 120V on primary side of external transformer (if NO, fix wiring between panel and transformer). If 120V is present, check for 24V on secondary side (if NO, replace External Transformer #4000-01V). If 24V is present, check for 24V to the thermostat (if YES, replace/repair thermostat or wiring; if NO, fix wiring between transformer and thermostat).
- If YES: Check if power across the 24V wire on the circuit board and ground is 24V. If NO, check for 120V on primary side of internal transformer (if NO, repair wiring; if YES, replace internal transformer). If 24V is present, check t-stat wire to ground (if NO, replace relay board). If YES, check if circuit board sends 120V to fan (if NO, check if pressure switch is stuck closed and replace switch or Circuit Board #TP-851B; if YES, remove fan obstruction or replace Inducer Fan Blower #TP-55A).
- Without HLRP Isolation Relays: Check if power across the left terminal of the 24V plug and ground is 24V.
- If NO: Check for 120V on primary side of internal transformer (if NO, repair wiring). If 120V is present, check for 24V on secondary side (if NO, replace internal transformer; if YES, repair wiring between transformer and 24V terminal plug).
- If YES: Check if power across the middle (low) terminal of the 24V plug and ground (screw on Burner Control Box) is 24V (if NO, repair thermostat or wiring to heater). If YES, check for 24V across TH and ground terminals on circuit board (if NO, correct wiring). If YES, check if circuit board sends 120V to fan (if YES, remove fan obstruction or replace Inducer Fan Blower #TP-55A). If board is not sending 120V to fan, check if pressure switch is stuck closed (if YES, replace pressure switch). If not stuck, check loose wiring or hose restrictions to pressure switch (if bad, replace wiring/hoses). If OK, check for a 2-flash APS code after 0–30 seconds (if NO, replace Circuit Board #TP-851B; if YES, verify baffles, clean blower/intake/exhaust, 4" intake pipe ≤20 ft and ≤2 elbows, and no negative air pressure, then replace pressure switch by BTU rating: Part #TP-264D for 50–75 MBH, Part #TP-1264A for 100–125 MBH, or Part #TP-264F for 150–200 MBH).
- With HLRP Isolation Relays: Check for 24V from the thermostat.
- If YES: Proceed to Step 2.
2. Does the switch light energize?
- If NO: Check if the green light is burnt out (if burnt out, replace with Green Indicator Light #TP-1428). If not burnt out, check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, follow the 24V plug/pressure switch checks above).
- If YES: Proceed to Step 3.
3. Does the igniter warm up and glow red?
- If NO: Check if the igniter is physically damaged (if YES, replace with Part #TP-50A Glo-Bar Hot Surface Igniter, replaces TP-50). If undamaged, check voltage at igniter sequence (5–15 seconds after power to heater) for 120V.
- If NO: Check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, check 24V plug/pressure switch circuit).
- If YES: Check resistance through the igniter—must be 50–400 Ω (if out of range, replace with Part #TP-50A Glo-Bar Hot Surface Igniter; if in range, proceed to Step 4).
- If YES: Proceed to Step 4.
4. After igniter warms up, does the gas valve open & burner light?
- If Gas Valve Does NOT Open: Test for 24V at valve opening period (45–60 seconds after power) for 8 seconds (if NO, replace Circuit Board #TP-851B; if YES, verify gas pressure is within rating plate min/max inputs and replace gas valve: Part #TP-3140 for Natural Gas or Part #TP-3141 for Propane/LP).
- If Burner Does NOT Light: Verify ball/shut-off valve is ON and gas pressure matches rating plate min/max inputs. If pressure is OK, verify gas lines were purged of air (if NO, purge gas line; if YES, replace gas valve: Part #TP-3140 Natural Gas or Part #TP-3141 Propane/LP).
5. Does the burner stay on?
- If it shuts off after ~8 seconds: Check proper grounding and polarity. Using a microampmeter, check DC amperage at flame rod—must be greater than 1.0 microamps (if NO, check gas pressure and replace Flame Sensor Rod #TP-222; if YES, verify flame sensor wire and replace Circuit Board #TP-851B).
- If it turns on and off immediately (1–2 seconds): Verify gas pressure matches rating plate; if OK, exhaust may be restricted or pressure switch is faulty (#TP-264D 50–75 MBH, #TP-1264A 100–125 MBH, #TP-264F 150–200 MBH).
- If it shuts down before call for heat ends: Check for improper grounding, high winds, attic combustion air, dirty environment, improperly positioned baffles, or fluctuating gas pressure.
6. High Fire Mode Check (If Heater Won't Enter High Fire)
- Verify Manifold Pressure: High fire is 3.3" to 3.5" WC (Natural Gas) or 9" to 10" WC (Propane)—if already at these pressures, replace Amber Indicator Light #TP-828.
- If in Low Fire Mode (2.0"–2.5" WC Natural Gas / 5.0"–6.5" WC Propane): Check for 24V across GROUND and HIGH (HIGH to COM on HLRP relay models) on the exterior control box terminal strip (if NO, repair/replace wiring or thermostat). If YES, measure voltage across the red wire on VALVE to GROUND (red wire on RELAY to GROUND on relay models): if 24V, replace gas valve (#TP-3140 Nat Gas or #TP-3141 LP); if not 24V, replace relay.
HL3 10/2012 to 07/2014b
Troubleshooting Guide
HL3 Series (07/2008 to 09/2012) Lockout & LED Codes
Scroll down inside this box for text steps & direct replacement part links:
Safety Notice: Bypassing any switch is intended for testing purposes only. Do not leave any switch bypassed during normal operation or the heater's built-in safety mechanisms will be compromised.
- Soft Lockout: Heater attempts to light 3 times. On ignition failure (gas pressure, valve, no flame sense), it enters a 15-minute soft lockout and tries 3 more times before entering Hard Lockout.
- Hard Lockout: Triggered if proof of flame is not established, a component fails, or blockages occur. Reset by briefly interrupting the power source.
- Operational Indicator Lights (Figure 3.1): Light 1 (Amber/Yellow Light #TP-828) = Low Fire Mode; Light 2 (Amber/Yellow Light #TP-828) = High Fire Mode; Light 3 (Green Light #TP-1428) = Pressure Switch Closes.
HL3 Series (07/2008 to 09/2012) LED Fault Code Status (Chart 3.1)
| LED Code | Fault Status | Fault Code Delay |
|---|---|---|
| Initial flash on power up, then steady off | No fault, normal operation | No delay |
| Steady ON | Module failure / Internal fault (Circuit Board #TP-851B) | No delay |
| 1 flash | Ignition failure | 3 minutes |
| 2 flashes | APS (Air Proving Switch) (Fan / Intake / Exhaust) | 0–30 seconds |
| 3 flashes | Lockout | 17 minutes |
| 4 flashes | Solenoid valve fault / Leaky valve / Flame amplifier fault | No delay |
| No flash on 117V startup | Transformer fault | No delay |
HL3 Series (07/2008 to 09/2012) Step-by-Step Troubleshooting Flowchart
Start: Turn up the thermostat.
1. Does the fan blower turn on?
- If NO: Check if power at the heater is 120V.
- If NO (Not 120V): Find the source of the electrical problem between the panel and heater.
- If YES (120V present): Check if the heater has Optional HLRP Isolation Relays (External Relay Kit #ERK, identified with an orange crescent around the terminal plug).
- With HLRP Isolation Relays: Check for 24V from the thermostat.
- If NO: Check for 120V on primary side of external transformer (if NO, fix wiring between panel and transformer). If 120V is present, check for 24V on secondary side (if NO, replace External Transformer #4000-01V). If 24V is present, check for 24V to the thermostat (if YES, replace/repair thermostat or wiring; if NO, fix wiring between transformer and thermostat).
- If YES: Check if power across the 24V wire on the circuit board and ground is 24V. If NO, check for 120V on primary side of internal transformer (if NO, repair wiring; if YES, replace internal transformer). If 24V is present, check t-stat wire to ground (if NO, replace relay board). If YES, check if circuit board sends 120V to fan (if NO, check if pressure switch is stuck closed and replace switch or Circuit Board #TP-851B; if YES, remove fan obstruction or replace Inducer Fan Blower #TP-55A).
- Without HLRP Isolation Relays: Check if power across the left terminal of the 24V plug and ground is 24V.
- If NO: Check for 120V on primary side of internal transformer (if NO, repair wiring). If 120V is present, check for 24V on secondary side (if NO, replace internal transformer; if YES, repair wiring between transformer and 24V terminal plug).
- If YES: Check if power across the middle (low) terminal of the 24V plug and ground (screw on Burner Control Box) is 24V (if NO, repair thermostat or wiring to heater). If YES, check for 24V across TH and ground terminals on circuit board (if NO, correct wiring). If YES, check if circuit board sends 120V to fan (if YES, remove fan obstruction or replace Inducer Fan Blower #TP-55A). If board is not sending 120V to fan, check if pressure switch is stuck closed (if YES, replace pressure switch). If not stuck, check loose wiring or hose restrictions to pressure switch (if bad, replace wiring/hoses). If OK, check for a 2-flash APS code after 0–30 seconds (if NO, replace Circuit Board #TP-851B; if YES, verify baffles, clean blower/intake/exhaust, 4" intake pipe ≤20 ft and ≤2 elbows, and no negative air pressure, then replace pressure switch by BTU rating: Part #TP-264D for 50–75 MBH, Part #TP-1264A for 100–125 MBH, or Part #TP-264F for 150–200 MBH).
- With HLRP Isolation Relays: Check for 24V from the thermostat.
- If YES: Proceed to Step 2.
2. Does the switch light energize?
- If NO: Check if the green light is burnt out (if burnt out, replace with Green Indicator Light #TP-1428). If not burnt out, check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, follow the 24V plug/pressure switch checks above).
- If YES: Proceed to Step 3.
3. Does the igniter warm up and glow red?
- If NO: Check if the igniter is physically damaged (if YES, replace with Part #TP-50A Glo-Bar Hot Surface Igniter, replaces TP-50). If undamaged, check voltage at igniter sequence (5–15 seconds after power to heater) for 120V.
- If NO: Check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, check 24V plug/pressure switch circuit).
- If YES: Check resistance through the igniter—must be 50–400 Ω (if out of range, replace with Part #TP-50A Glo-Bar Hot Surface Igniter; if in range, proceed to Step 4).
- If YES: Proceed to Step 4.
4. After igniter warms up, does the gas valve open & burner light?
- If Gas Valve Does NOT Open: Test for 24V at valve opening period (45–60 seconds after power) for 8 seconds (if NO, replace Circuit Board #TP-851B; if YES, verify gas pressure is within rating plate min/max inputs and replace gas valve: Part #TP-3140 for Natural Gas or Part #TP-3141 for Propane/LP).
- If Burner Does NOT Light: Verify ball/shut-off valve is ON and gas pressure matches rating plate min/max inputs. If pressure is OK, verify gas lines were purged of air (if NO, purge gas line; if YES, replace gas valve: Part #TP-3140 Natural Gas or Part #TP-3141 Propane/LP).
5. Does the burner stay on?
- If it shuts off after ~8 seconds: Check proper grounding and polarity. Using a microampmeter, check DC amperage at flame rod—must be greater than 1.0 microamps (if NO, check gas pressure and replace Flame Sensor Rod #TP-222; if YES, verify flame sensor wire and replace Circuit Board #TP-851B).
- If it turns on and off immediately (1–2 seconds): Verify gas pressure matches rating plate; if OK, exhaust may be restricted or pressure switch is faulty (#TP-264D 50–75 MBH, #TP-1264A 100–125 MBH, #TP-264F 150–200 MBH).
- If it shuts down before call for heat ends: Check for improper grounding, high winds, attic combustion air, dirty environment, improperly positioned baffles, or fluctuating gas pressure.
6. High Fire Mode Check (If Heater Won't Enter High Fire)
- Verify Manifold Pressure: High fire is 3.3" to 3.5" WC (Natural Gas) or 9" to 10" WC (Propane)—if already at these pressures, replace Amber Indicator Light #TP-828.
- If in Low Fire Mode (2.0"–2.5" WC Natural Gas / 5.0"–6.5" WC Propane): Check for 24V across GROUND and HIGH (HIGH to COM on HLRP relay models) on the exterior control box terminal strip (if NO, repair/replace wiring or thermostat). If YES, measure voltage across the red wire on VALVE to GROUND (red wire on RELAY to GROUND on relay models): if 24V, replace gas valve (#TP-3140 Nat Gas or #TP-3141 LP); if not 24V, replace relay.
HL3 07/2008 to 09/2012
Troubleshooting Guide
HL3 Series (07/2008 to 09/2012) Lockout & LED Codes
Scroll down inside this box for text steps & direct replacement part links:
Safety Notice: Bypassing any switch is intended for testing purposes only. Do not leave any switch bypassed during normal operation or the heater's built-in safety mechanisms will be compromised.
- Soft Lockout: Heater attempts to light 3 times. On ignition failure (gas pressure, valve, no flame sense), it enters a 15-minute soft lockout and tries 3 more times before entering Hard Lockout.
- Hard Lockout: Triggered if proof of flame is not established, a component fails, or blockages occur. Reset by briefly interrupting the power source.
- Operational Indicator Lights (Figure 3.1): Light 1 (Amber/Yellow Light #TP-828) = Low Fire Mode; Light 2 (Amber/Yellow Light #TP-828) = High Fire Mode; Light 3 (Green Light #TP-1428) = Pressure Switch Closes.
HL3 Series (07/2008 to 09/2012) LED Fault Code Status (Chart 3.1)
| LED Code | Fault Status | Fault Code Delay |
|---|---|---|
| Initial flash on power up, then steady off | No fault, normal operation | No delay |
| Steady ON | Module failure / Internal fault (Circuit Board #TP-851B) | No delay |
| 1 flash | Ignition failure | 3 minutes |
| 2 flashes | APS (Air Proving Switch) (Fan / Intake / Exhaust) | 0–30 seconds |
| 3 flashes | Lockout | 17 minutes |
| 4 flashes | Solenoid valve fault / Leaky valve / Flame amplifier fault | No delay |
| No flash on 117V startup | Transformer fault | No delay |
HL3 Series (07/2008 to 09/2012) Step-by-Step Troubleshooting Flowchart
Start: Turn up the thermostat.
1. Does the fan blower turn on?
- If NO: Check if power at the heater is 120V.
- If NO (Not 120V): Find the source of the electrical problem between the panel and heater.
- If YES (120V present): Check if the heater has Optional HLRP Isolation Relays (External Relay Kit #ERK, identified with an orange crescent around the terminal plug).
- With HLRP Isolation Relays: Check for 24V from the thermostat.
- If NO: Check for 120V on primary side of external transformer (if NO, fix wiring between panel and transformer). If 120V is present, check for 24V on secondary side (if NO, replace External Transformer #4000-01V). If 24V is present, check for 24V to the thermostat (if YES, replace/repair thermostat or wiring; if NO, fix wiring between transformer and thermostat).
- If YES: Check if power across the 24V wire on the circuit board and ground is 24V. If NO, check for 120V on primary side of internal transformer (if NO, repair wiring; if YES, replace internal transformer). If 24V is present, check t-stat wire to ground (if NO, replace relay board). If YES, check if circuit board sends 120V to fan (if NO, check if pressure switch is stuck closed and replace switch or Circuit Board #TP-851B; if YES, remove fan obstruction or replace Inducer Fan Blower #TP-55A).
- Without HLRP Isolation Relays: Check if power across the left terminal of the 24V plug and ground is 24V.
- If NO: Check for 120V on primary side of internal transformer (if NO, repair wiring). If 120V is present, check for 24V on secondary side (if NO, replace internal transformer; if YES, repair wiring between transformer and 24V terminal plug).
- If YES: Check if power across the middle (low) terminal of the 24V plug and ground (screw on Burner Control Box) is 24V (if NO, repair thermostat or wiring to heater). If YES, check for 24V across TH and ground terminals on circuit board (if NO, correct wiring). If YES, check if circuit board sends 120V to fan (if YES, remove fan obstruction or replace Inducer Fan Blower #TP-55A). If board is not sending 120V to fan, check if pressure switch is stuck closed (if YES, replace pressure switch). If not stuck, check loose wiring or hose restrictions to pressure switch (if bad, replace wiring/hoses). If OK, check for a 2-flash APS code after 0–30 seconds (if NO, replace Circuit Board #TP-851B; if YES, verify baffles, clean blower/intake/exhaust, 4" intake pipe ≤20 ft and ≤2 elbows, and no negative air pressure, then replace pressure switch by BTU rating: Part #TP-264D for 50–75 MBH, Part #TP-1264A for 100–125 MBH, or Part #TP-264F for 150–200 MBH).
- With HLRP Isolation Relays: Check for 24V from the thermostat.
- If YES: Proceed to Step 2.
2. Does the switch light energize?
- If NO: Check if the green light is burnt out (if burnt out, replace with Green Indicator Light #TP-1428). If not burnt out, check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, follow the 24V plug/pressure switch checks above).
- If YES: Proceed to Step 3.
3. Does the igniter warm up and glow red?
- If NO: Check if the igniter is physically damaged (if YES, replace with Part #TP-50A Glo-Bar Hot Surface Igniter, replaces TP-50). If undamaged, check voltage at igniter sequence (5–15 seconds after power to heater) for 120V.
- If NO: Check if inlet or outlet is plugged/obstructed (remove obstruction if blocked; if clear, check 24V plug/pressure switch circuit).
- If YES: Check resistance through the igniter—must be 50–400 Ω (if out of range, replace with Part #TP-50A Glo-Bar Hot Surface Igniter; if in range, proceed to Step 4).
- If YES: Proceed to Step 4.
4. After igniter warms up, does the gas valve open & burner light?
- If Gas Valve Does NOT Open: Test for 24V at valve opening period (45–60 seconds after power) for 8 seconds (if NO, replace Circuit Board #TP-851B; if YES, verify gas pressure is within rating plate min/max inputs and replace gas valve: Part #TP-3140 for Natural Gas or Part #TP-3141 for Propane/LP).
- If Burner Does NOT Light: Verify ball/shut-off valve is ON and gas pressure matches rating plate min/max inputs. If pressure is OK, verify gas lines were purged of air (if NO, purge gas line; if YES, replace gas valve: Part #TP-3140 Natural Gas or Part #TP-3141 Propane/LP).
5. Does the burner stay on?
- If it shuts off after ~8 seconds: Check proper grounding and polarity. Using a microampmeter, check DC amperage at flame rod—must be greater than 1.0 microamps (if NO, check gas pressure and replace Flame Sensor Rod #TP-222; if YES, verify flame sensor wire and replace Circuit Board #TP-851B).
- If it turns on and off immediately (1–2 seconds): Verify gas pressure matches rating plate; if OK, exhaust may be restricted or pressure switch is faulty (#TP-264D 50–75 MBH, #TP-1264A 100–125 MBH, #TP-264F 150–200 MBH).
- If it shuts down before call for heat ends: Check for improper grounding, high winds, attic combustion air, dirty environment, improperly positioned baffles, or fluctuating gas pressure.
6. High Fire Mode Check (If Heater Won't Enter High Fire)
- Verify Manifold Pressure: High fire is 3.3" to 3.5" WC (Natural Gas) or 9" to 10" WC (Propane)—if already at these pressures, replace Amber Indicator Light #TP-828.
- If in Low Fire Mode (2.0"–2.5" WC Natural Gas / 5.0"–6.5" WC Propane): Check for 24V across GROUND and HIGH (HIGH to COM on HLRP relay models) on the exterior control box terminal strip (if NO, repair/replace wiring or thermostat). If YES, measure voltage across the red wire on VALVE to GROUND (red wire on RELAY to GROUND on relay models): if 24V, replace gas valve (#TP-3140 Nat Gas or #TP-3141 LP); if not 24V, replace relay.